MV Lead Sheathed

The core of our MV Lead Sheathed cables is provided by an impermeable and watertight lead alloy sheath to counter the corrosive effect of chemicals involved in these industries where the lead sheath thickness complies with IEC 60502-2. The lead sheathing’s resistance to sulfides, water, oil and corrosive chemicals found in the ground water, gives these cables an extended lifespan, making them a reliable option for large-scale, infrastructure-related uses.

At ARABIAN EXPERTS Cables, our range of Medium Voltage Lead Sheathed Cables comply with IEC 60502-2 requirements. In addition, the lead sheath is made of cable grade alloys in line with BS EN 12548.

Our cables come with a standard outer sheath made of extruded PVC/ST2 or PE/ST7 as per IEC 60502-2. Special requests can also be accommodated for the outer sheathing of our MV Lead Sheathed Cables. We are able to supply fire retardant PVC, anti-termite/anti-rodent PVC, sunlight resistant PVC, and oil resistant PVC.

20160831_MV-sheathead-725

UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE

COPPER CONDUCTORS

STANDARD : IEC 60502-2

Uo/U (Um)=3.5/6(7.2) kV

  • REQUEST A QUOTE
 

 

Code Number (1)Nominal Cross SectionNominal Dia. of Cond.Weight of Cond.Nominal Insulation Thick.Approx. diameter over insulationNominal Lead Sheath Thick.Nominal PVC Sheath Thick.Approx. External DiameterApprox. Weight of Cable
 mm²mmkg/kmmmmmmmmmmmkg/km
10255.92202.512.11.21.6221280
11356.93052.513.11.21.6231440
12508.14142.514.31.31.7251720
13709.75982.515.91.31.7272030
149511.48272.517.61.41.8292495
1512012.910432.519.11.41.8312830
1615014.312872.520.51.51.9323310
1718516.016102.522.21.51.9343790
1824018.421162.624.81.62.0374620
1930020.726502.827.71.62.1415560
2040023.233843.030.61.72.2456760
2150026.743523.234.51.82.3498230
2263030.556233.238.31.92.55410200
Nominal Cross SectionDC Resistance at 20°CInductanceCapacitanceShort circuit current for 1 sec.Current Carrying Capacity(2)Voltage drop per phase
TrefoilFlatConductorScreenUnder- ground CableCable in Air
mm²ohm/kmmH/kmmH/kmµF/KmKAKAAAV/A/km
250.7270.4440.7600.263.5751.4571601700.842
350.5240.4260.7450.295.0051.5431952000.632
500.3870.4080.7200.327.1501.7932302350.488
700.2680.3880.6940.3710.0101.9242852950.362
950.1930.3780.6790.3913.5852.2733403600.283
1200.1530.3640.6600.4417.1602.4243854200.239
1500.1240.3540.6450.4821.4502.7594304750.208
1850.09910.3430.6300.5226.4552.9244855500.180
2400.07540.3320.6110.5634.3203.4885606500.154
3000.06010.3240.5960.5842.9003.8286307400.137
4000.0470.3130.5780.6157.2004.4337208600.122
5000.03660.3060.5640.6471.5005.2118009900.111
6300.02830.2960.5480.7190.0906.11591011400.1021

1. The code numbers to be read in conjuction with 02020701 at the beginning.

Code number for different types of insulation screen : replace the 6th digit as follows:
7 for STRIPPABLE + LEAD; 8 for BONDED + LEAD; 9 for GRAPHITE + LEAD

Example: for 150 mm² Strippable + Lead cable, the code number is 0202070116.

2. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

For other laying conditions, please refer to Table nos. 1 – 5 for derating factors.

UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE

COPPER CONDUCTORS

STANDARD : IEC 60502-2

Uo/U (Um)=6/10(12) kV

  • REQUEST A QUOTE
 

Code Number (1)Nominal Cross SectionNominal Dia. of Cond.Weight of Cond.Nominal Insulation Thick.Approx. diameter over insulationNominal Lead Sheath Thick.Nominal PVC Sheath Thick.Approx. External DiameterApprox. Weight of Cable
 mm²mmkg/kmmmmmmmmmmmkg/km
10255.92203.413.91.31.6241500
11356.93053.414.91.31.7261670
12508.14143.416.11.31.7271870
13709.75983.417.71.41.8292290
149511.48273.419.41.41.8312660
1512012.910433.420.91.51.9333120
1615014.312873.422.31.51.9343500
1718516.016103.424.01.62.0374100
1824018.421163.426.41.62.1404900
1930020.726503.428.91.72.1435840
2040023.233843.431.41.82.1467000
2150026.743523.434.91.92.4508450
2263030.556233.438.71.92.5559600
Nominal Cross SectionDC Resistance at 20°CInductanceCapacitanceShort circuit current for 1 sec.Current Carrying Capacity(2)Voltage drop per phase
TrefoilFlatConductorScreenUnder- ground CableCable in Air
mm²ohm/kmmH/kmmH/km µF/KmKAKAAAV/A/km
250.7270.4600.7700.213.5751.7551601700.846
350.5240.4400.7510.235.0051.8491952000.635
500.3870.420726.0000.257.1501.9612302350.490
700.2680.4010.7000.2910.0102.2832852950.364
950.1930.3830.6910.3113.5852.4543403600.284
1200.1530.3760.6660.3417.1602.8023854200.242
1500.1240.3640.6500.3721.4502.9534304750.210
1850.09910.3540.6350.4026.4553.3564855500.183
2400.07540.3410.6150.4534.3203.6785606500.156
3000.06010.3290.5930.4942.9004.2266307400.138
4000.0470.3180.5800.5557.2004.8107208600.123
5000.03660.3080.5650.6071.5005.5698009900.111
6300.02830.2990.5490.6890.0906.17091011400.103

1. The code numbers to be read in conjuction with 03020701 at the beginning.

Code number for different types of insulation screen : replace the 6th digit as follows: 7 for STRIPPABLE + LEAD; 8 for BONDED + LEAD; 9 for GRAPHITE + LEAD

Example: for 150 mm² Strippable + Lead cable, the code number is 0302070116.

2. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

For other laying conditions, please refer to Table nos. 1 – 5 for derating factors.

UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE

COPPER CONDUCTORS

STANDARD : IEC 60502-2

Uo/U (Um)=8.7/15(17.5) kV

  • REQUEST A QUOTE
 

Code Number (1)Nominal Cross SectionNominal Dia. of Cond.Weight of Cond.Nominal Insulation Thick.Approx. diameter over insulationNominal Lead Sheath Thick.Nominal PVC Sheath Thick.Approx. External DiameterApprox. Weight of Cable
 mm²mmkg/kmmmmmmmmmmmkg/km
10255.92204.516.11.31.7271700
11356.93054.517.11.41.8281950
12508.14144.518.31.41.8302150
13709.75984.519.91.41.8312450
149511.48274.521.61.51.9342950
1512012.910434.523.11.52.0353350
1615014.312874.524.51.620.0373850
1718516.016104.526.21.62.1404400
1824018.421164.528.61.72.2425300
1930020.726504.531.11.72.2456000
2040023.233844.533.61.82.3487200
2150026.743524.537.11.92.4528700
2263030.556234.540.92.02.65710700
Nominal Cross SectionDC Resistance at 20°CInductanceCapacitanceShort circuit current for 1 sec.Current Carrying Capacity(2)Voltage drop per phase
TrefoilFlatConductorScreenUnder- ground CableCable in Air
mm²ohm/kmmH/kmmH/km µF/KmKAKAAAV/A/km
250.7270.4700.7800.173.5751.9611651700.850
350.5240.4560.7580.195.0052.2231952000.638
500.3870.4350.7320.217.1502.3432302450.494
700.2680.4150.7060.2310.0102.5042803050.368
950.1930.4020.6900.2513.5852.8773353750.289
1200.1530.3890.6720.2717.1603.0393854250.245
1500.1240.3770.6560.2921.4503.4144304850.213
1850.09910.3660.6410.3226.4553.6554905600.185
2400.07540.3520.6210.3534.3204.1895606600.159
3000.06010.3400.6050.3942.9004.4956407500.141
4000.0470.3270.5850.4357.2005.0957208700.125
5000.03660.3180.5700.4871.5005.87081010000.114
6300.02830.3070.5540.5390.0906.82591011500.105

1. The code numbers to be read in conjuction with 04020701 at the beginning.

Code number for different types of insulation screen : replace the 6th digit as follows:
7 for STRIPPABLE + LEAD; 8 for BONDED + LEAD; 9 for GRAPHITE + LEAD

Example: for 150 mm² Strippable + Lead cable, the code number is 0402070116.

2. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

For other laying conditions, please refer to Table nos. 1 – 5 for derating factors.

UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE

COPPER CONDUCTORS

STANDARD : IEC 60502-2

Uo/U (Um)=6/10(12) kV

  • REQUEST A QUOTE
 

Code Number (1)Nominal Cross SectionNominal Dia. of Cond.Weight of Cond.Nominal Insulation Thick.Approx. diameter over insulationNominal Lead Sheath Thick.Nominal PVC Sheath Thick.Approx. External DiameterApprox. Weight of Cable
 mm²mmkg/kmmmmmmmmmmmkg/km
10255.96703.413.91.82.4505150
11356.99293.414.91.92.5535900
12508.112603.416.12.02.6566800
13709.718203.417.72.12.8608150
149511.425183.419.42.22.9659650
1512012.931753.420.92.33.06911150
1615014.339193.422.32.43.17212650
1718516.049023.424.02.53.27714600
1824018.464433.426.42.63.48417650
1930020.780693.428.92.83.69121050
Nominal Cross SectionDC Resistance at 20°CNominal InductanceCapacitanceShort circuit current for 1 sec.Current Carrying Capacity(3)Voltage drop per phase
ConductorScreen per phase (2)Under- ground CableCable in Air
mm²ohm/kmmH/km µF/KmKAKAAAV/A/km
250.7270.3310.213.5750.5031501500.816
350.5240.3180.235.0050.5351901900.607
500.3870.3050.257.1500.5742252250.464
700.2680.2920.2910.0100.6252752800.340
950.1930.2850.3113.5850.6803303400.262
1200.1530.2760.3417.1600.7283703850.219
1500.1240.2690.3721.4500.7734204450.189
1850.09910.2630.4026.4550.8274705100.162
2400.07540.2550.4434.3200.9175405900.132
3000.06010.2480.4842.9000.9975806200.120

1. The code numbers to be read in conjuction with 03020103 at the beginning and “L” at the end.

Example: for 150 mm² the code number is 0302010316L

Code number for different types of insulation screen : replace the 6th digit as follows:
2 for S + CUW; 3 for B + CUT; 4 for B + CUW; 5 for G + CUT and 6 for G + CUW

2. For Copper Tape screen only.

3. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

For other laying conditions, please refer to Table nos. 1 – 5 for derating factors.

ARMOURED SINGLE CORE LEAD SHEATHED CABLE

COPPER CONDUCTORS

STANDARD : IEC 60502-2

Uo/U (Um)=6/10(12) kV

  • REQUEST A QUOTE
 

Code Number (1)Nominal Cross SectionNominal Dia. of Cond.Weight of Cond.Nominal Insulation Thick.Approx. diameter over insulationNominal Lead Sheath Thick.Nom. Dia. of Alum. WireNominal PVC Sheath Thick.Approx. External DiameterApprox. Weight of Cable
 mm²mmkg/kmmmmmmmmmmmmmkg/km
10255.92203.413.91.31.61.8301950
11356.93053.414.91.31.61.9322100
12508.14143.416.11.31.61.9332350
13709.75983.417.71.41.62.0352750
149511.48273.419.41.42.02.0383300
1512012.910433.420.91.52.02.1403800
1615014.312873.422.31.52.02.1414200
1718516.016103.424.01.62.02.2444850
1824018.421163.426.41.62.02.3475700
1930020.726503.428.91.72.52.4516850
2040023.233843.431.41.82.52.5548050
2150026.743523.434.91.92.52.6599700
2263030.556233.438.71.92.52.76311600
Nominal Cross SectionDC Resistance at 20°CInductanceCapacitanceShort circuit current for 1 sec.Current Carrying Capacity(2)Voltage drop per phase
TrefoilFlatConductorScreenUnder- ground CableCable in Air
mm²ohm/kmmH/kmmH/km µF/KmKAKAAAV/A/km
250.7270.4880.7900.213.5751.7551501550.852
350.5240.4720.7650.235.0051.8491952000.642
500.3870.4500.7390.257.1501.9612302350.497
700.2680.4280.7130.2910.0102.2832852950.370
950.1930.4160.6970.3113.5852.4543403600.292
1200.1530.4010.6780.3417.1602.8023854200.246
1500.1240.3900.6630.3721.4502.9534304750.216
1850.09910.3780.6470.4026.4553.3564855500.188
2400.07540.3630.6270.4534.3203.6785606500.161
3000.06010.3510.6110.4942.9004.2266307400.143
4000.0470.3380.5910.5557.2004.8107208600.128
5000.03660.3280.5760.6071.5005.5698009900.116
6300.02830.3170.5600.6890.0906.17091011400.107

1. The code numbers to be read in conjuction with 03020711 at the beginning.

Code number for different types of insulation screen : replace the 6th digit as follows: 7 for STRIPPABLE + LEAD; 8 for BONDED + LEAD; 9 for GRAPHITE + LEAD

Example: for 150 mm² Strippable + Lead cable, the code number is 0302071116.

2. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

For other laying conditions, please refer to Table nos. 1 – 5 for derating factors.

ARMOURED SINGLE CORE LEAD SHEATHED CABLE

COPPER CONDUCTORS

STANDARD : IEC 60502-2

Uo/U (Um)=8.7/15(17.5) kV

 

Code Number (1)Nominal Cross SectionNominal Dia. of Cond.Weight of Cond.Nominal Insulation Thick.Approx. diameter over insulationNominal Lead Sheath Thick.Nom. Dia. of Alum. WireNominal PVC Sheath Thick.Approx. External DiameterApprox. Weight of Cable
 mm²mmkg/kmmmmmmmmmmmmmkg/km
10255.92204.516.11.31.61.9332150
11356.93054.517.11.41.61.9342450
12508.14144.518.31.41.62.0362700
13709.75984.519.91.42.02.1393200
149511.48274.521.61.52.02.1413700
1512012.910434.523.11.52.02.2424100
1615014.312874.524.51.62.02.2444600
1718516.016104.526.21.62.02.3475200
1824018.421164.528.61.72.52.4516350
1930020.726504.531.11.72.52.5547200
2040023.233844.533.61.82.52.6578450
2150026.743524.537.11.92.52.76110100
2263030.556234.540.92.02.52.86612200
Nominal Cross SectionDC Resistance at 20°CInductanceCapacitanceShort circuit current for 1 sec.Current Carrying Capacity(2)Voltage drop per phase
TrefoilFlatConductorScreenUnder- ground CableCable in Air
mm²ohm/kmmH/kmmH/kmµF/KmKAKAAAV/A/km
250.7270.5050.7960.173.5751.9611501700.856
350.5240.4840.7710.195.0052.2231952000.645
500.3870.4630.7450.217.1502.3532302450.500
700.2680.4410.7190.2310.0102.5042803050.373
950.1930.4280.7030.2513.5852.8773353750.294
1200.1530.4130.6840.2717.1603.0393854250.250
1500.1240.4010.6680.2921.4503.4144304850.219
1850.09910.3880.6520.3226.4553.6554905600.190
2400.07540.3730.6320.3534.3204.1895606600.163
3000.06010.3610.6160.3942.9004.4956407500.146
4000.0470.3460.5960.4357.2005.0957208700.130
5000.03660.3370.5820.4871.5005.87081010000.118
6300.02830.3250.5650.5390.0906.82591011500.109

1. The code numbers to be read in conjuction with 04020711 at the beginning.

Code number for different types of insulation screen : replace the 6th digit as follows: 7 for STRIPPABLE + LEAD; 8 for BONDED + LEAD; 9 for GRAPHITE + LEAD

Example: for 150 mm² Strippable + Lead cable, the code number is 0402071116.

2. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

For other laying conditions, please refer to Table nos. 1 – 5 for derating factors.

UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE

COPPER CONDUCTORS

STANDARD : IEC 60502-2 

Uo/U (Um)=12/20(24) kV

  • REQUEST A QUOTE
 

Code Number (1)Nominal Cross SectionNominal Dia. of Cond.Weight of Cond.Nominal Insulation Thick.Approx. diameter over insulationNominal Lead Sheath Thick.Nominal PVC Sheath Thick.Approx. External DiameterApprox. Weight of Cable
 mm²mmkg/kmmmmmmmmmmmkg/km
10255.92206.019.11.41.8312050
11356.93055.519.11.41.8312150
12508.14145.520.31.51.9322450
13709.75985.521.91.51.9342800
149511.48275.523.61.62.0363300
1512012.910435.525.11.62.0383700
1615014.312875.526.51.62.1404150
1718516.016105.528.21.72.1424700
1824018.421165.530.61.72.2455450
1930020.726505.533.11.82.3486450
2040023.233845.535.61.92.4517600
2150026.743525.539.12.02.5559300
2263030.556235.542.92.12.66011150
Nominal Cross SectionDC Resistance at 20°CInductanceCapacitanceShort circuit current for 1 sec.Current Carrying Capacity(2)Voltage drop per phase
TrefoilFlatConductorScreenUnder- ground CableCable in Air
mm²ohm/kmmH/kmmH/kmµF/KmKAKAAAV/A/km
250.7270.4970.7920.143.5752.4241651700.854
350.5240.4680.7630.165.0052.4241952000.641
500.3870.4480.7380.187.1502.7372301450.497
700.2680.4260.7120.2010.0102.9102803050.370
950.1930.4140.6960.2113.5853.3103353750.291
1200.1530.3990.6770.2317.1603.4833854250.247
1500.1240.3880.6620.2521.4503.6904304850.216
1850.09910.3750.6460.2726.4554.1404905600.187
2400.07540.3610.6260.3034.3204.4335606600.161
3000.06010.3500.6100.3342.9005.0316407500.143
4000.0470.3360.5900.3757.2005.6657208700.127
5000.03660.3260.5750.4071.5006.56781010000.115
6300.02830.3150.5580.4590.0907.48391011501.070

1. The code numbers to be read in conjuction with 05020701 at the beginning.

Code number for different types of insulation screen : replace the 6th digit as follows:
7 for STRIPPABLE + LEAD; 8 for BONDED + LEAD; 9 for GRAPHITE + LEAD

Example: for 150 mm² Strippable + Lead cable, the code number is 0502070116. 

2. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

For other laying conditions, please refer to Table nos. 1 – 5 for derating factors.

UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE

COPPER CONDUCTORS

STANDARD : IEC 60502-2

Uo/U (Um)=18/30(36) kV

  • REQUEST A QUOTE
 

Code Number (1)Nominal Cross SectionNominal Dia. of Cond.Weight of Cond.Nominal Insulation Thick.Approx. diameter over insulationNominal Lead Sheath Thick.Nominal PVC Sheath Thick.Approx. External DiameterApprox. Weight of Cable
 mm²mmkg/kmmmmmmmmmmmkg/km
12508.14148.025.31.62.1383100
13709.75988.026.91.72.1403650
149511.48278.028.61.72.2424100
1512012.910438.030.11.72.2444450
1615014.312878.031.51.82.3465000
1718516.016108.033.21.82.3485500
1824018.421168.035.61.92.4516450
1930020.726508.038.12.02.5547500
2040023.233848.040.62.02.6578700
2150026.743528.044.12.12.76110250
2263030.556230.047.92.22.86612250
Nominal Cross SectionDC Resistance at 20°CInductanceCapacitanceShort circuit current for 1 sec.Current Carrying Capacity(2)Voltage drop per phase
TrefoilFlatConductorScreenUnder- ground CableCable in Air
mm²ohm/kmmH/kmmH/kmµF/KmKAKAAAV/A/km
500.3870.4820.7550.147.1503.5062302450.504
700.2680.4590.7280.1610.0103.9822803050.377
950.1930.4460.7120.1713.5854.1893353750.299
1200.1530.4300.6930.1817.1604.3723854250.254
1500.1240.4170.6770.1921.4504.8244304850.222
1850.09910.4040.6610.2126.4555.0434905600.194
2400.07540.3880.6410.2334.3205.6655606600.167
3000.06010.3750.6240.2542.9006.3376407500.149
4000.0470.3600.6040.2757.2006.7827208700.133
5000.03660.3490.5890.3071.5007.66481010000.121
6300.02830.3380.5700.3390.0908.64691011500.1121.

1. The code numbers to be read in conjuction with 06020701 at the beginning.

Code number for different types of insulation screen : replace the 6th digit as follows:
7 for STRIPPABLE + LEAD; 8 for BONDED + LEAD; 9 for GRAPHITE + LEAD

Example: for 150 mm² Strippable + Lead cable, the code number is 0602070116.

2. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

For other laying conditions, please refer to Table nos. 1 – 5 for derating factors.

  • UN-ARMOURED THREE CORE LEAD SHEATHED CABLE

    COPPER CONDUCTORS

    STANDARD : IEC 60502-2

    Uo/U (Um)=3.5/6(7.2) kV

    • REQUEST A QUOTE
     

    Code Number (1)Nominal Cross SectionNominal Dia. of Cond.Weight of Cond.Nominal Insulation Thick.Approx. diameter over insulationNominal Lead Sheath Thick.Nominal PVC Sheath Thick.Approx. External DiameterApprox. Weight of Cable
     mm²mmkg/kmmmmmmmmmmmkg/km
    10255.96702.512.11.62.2454300
    11356.99292.513.11.72.3484900
    12508.112602.514.31.82.4515800
    13709.718202.515.91.92.5557000
    149511.425182.517.62.02.6608400
    1512012.931752.519.12.12.7649700
    1615014.339192.520.52.12.86710950
    1718516.049022.522.22.23.07212750
    1824018.464432.624.82.43.27915750
    1930020.780692.827.72.63.38719250
    Nominal Cross SectionDC Resistance at 20°CNominal InductanceCapacitanceShort circuit current for 1 sec.Current Carrying Capacity(3)Voltage drop per phase
    ConductorScreen per phase (2)Under- ground CableCable in Air
    mm²ohm/kmmH/kmµF/KmKAKAAAV/A/km
    250.7270.3050.263.5750.4461501500.811
    350.5240.2940.295.0050.4781901900.602
    500.3870.2830.327.1500.5162252250.459
    700.2680.2720.3610.0100.5682752800.335
    950.1930.2660.3913.5850.6223303400.258
    1200.1530.2590.4317.1600.6703703850.215
    1500.1240.2530.4721.4500.7154204450.185
    1850.09910.2500.5226.4550.7704705100.159
    2400.07540.2430.5634.3200.8535405900.134
    3000.06010.2360.5842.9000.9595806200.1171.

    1. The code numbers to be read in conjuction with 02020103 at the beginning and “L” at the end.

    Example: for 150 mm² the code number is 0202010316L

    Code number for different types of insulation screen : replace the 6th digit as follows: 2 for S + CUW; 3 for B + CUT; 4 for B + CUW; 5 for G + CUT and 6 for G + CUW

    2. For Copper Tape screen only.

    3. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

    For other laying conditions, please refer to Table nos. 1 – 5 for derating factors.

ARMOURED SINGLE CORE LEAD SHEATHED CABLE

COPPER CONDUCTORS

STANDARD : IEC 60502-2

Uo/U (Um)=12/20(24) kV

  • REQUEST A QUOTE
 

Code Number (1)Nominal Cross SectionNominal Dia. of Cond.Weight of Cond.Nominal Insulation Thick.Approx. diameter over insulationNominal Lead Sheath Thick.Nom. Dia. of Alum. WireNominal PVC Sheath Thick.Approx. External DiameterApprox. Weight of Cable
 mm²mmkg/kmmmmmmmmmmmmmkg/km
10255.92206.019.11.42.02.0382750
11356.93055.519.11.42.02.0382800
12508.14145.520.31.52.02.1393150
13709.75985.521.91.52.02.1413550
149511.48275.523.61.62.02.2434100
1512012.910435.525.11.62.02.3454500
1615014.312875.526.51.62.02.3475000
1718516.016105.528.21.72.52.4505850
1824018.421165.530.61.72.52.5536650
1930020.726505.533.11.82.52.6567650
2040023.233845.535.61.92.52.7598950
2150026.743525.539.42.02.52.86410750
2263030.556235.542.92.12.52.96912800
Nominal Cross SectionDC Resistance at 20°CInductanceCapacitanceShort circuit current for 1 sec.Current Carrying Capacity(2)Voltage drop per phase
TrefoilFlatConductorScreenUnder- ground CableCable in Air
mm²ohm/kmmH/kmmH/kmµF/KmKAKAAAV/A/km
250.7270.5240.8050.143.5752.4241651700.860
350.5240.4960.7760.165.0052.4241952000.647
500.3870.4740.7510.187.1502.7372302450.502
700.2680.4520.7240.2010.0102.9102803050.376
950.1930.4380.7080.2113.5853.3103353750.299
1200.1530.4320.6890.2317.1603.4833854250.253
1500.1240.4100.6730.2521.4503.6904304850.221
1850.09910.3970.6570.2726.4554.1404905600.192
2400.07540.3820.6370.3034.3204.4335606600.165
3000.06010.3700.6210.3342.9005.0316407500.148
4000.0470.3550.6010.3757.2005.6657208700.132
5000.03660.3450.5860.4071.5006.56781010000.120
6300.02830.3330.5690.4590.0906.56791011500.111

1. The code numbers to be read in conjuction with 05020711 at the beginning.

Code number for different types of insulation screen : replace the 6th digit as follows: 7 for STRIPPABLE + LEAD; 8 for BONDED + LEAD; 9 for GRAPHITE + LEAD

Example: for 150 mm² Strippable + Lead cable, the code number is 0502071116.

2. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

For other laying conditions, please refer to Table nos. 1 – 5 for derating factors.

ARMOURED SINGLE CORE LEAD SHEATHED CABLE

COPPER CONDUCTORS

STANDARD : IEC 60502-2

Uo/U (Um)=18/30(36) kV

  • REQUEST A QUOTE
 

Code Number (1)Nominal Cross SectionNominal Dia. of Cond.Weight of Cond.Nominal Insulation Thick.Approx. diameter over insulationNominal Lead Sheath Thick.Nom. Dia. of Alum. WireNominal PVC Sheath Thick.Approx. External DiameterApprox. Weight of Cable
 mm²mmkg/kmmmmmmmmmmmmmkg/km
12508.14148.025.31.62.02.3453900
13709.75988.026.91.72.02.3484500
149511.48278.028.61.72.52.4515150
1512012.910438.030.11.72.52.5535600
1615014.312878.031.51.82.52.5546150
1718516.016108.033.21.82.52.6566750
1824018.421168.035.61.92.52.7597800
1930020.726508.038.12.02.52.8638900
2040023.233848.040.62.02.52.96610200
2150026.743528.044.12.12.53.07011900
2263030.556238.047.92.22.53.17513950
Nominal Cross SectionDC Resistance at 20°CInductanceCapacitanceShort circuit current for 1 sec.Current Carrying Capacity(2)Voltage drop per phase
TrefoilFlatConductorScreenUnder- ground CableCable in Air
mm²ohm/kmmH/kmmH/kmµF/KmKAKAAAV/A/km
500.3870.5040.7660.147.1503.5062302450.509
700.2680.4810.7400.1610.0103.9822803050.382
950.1930.4670.7230.1713.5854.1893353750.303
1200.1530.4500.7040.1817.1604.3723854250.259
1500.1240.4370.6880.1921.4504.8244304850.227
1850.09910.4240.6720.2126.4555.0434905600.198
2400.07540.4070.6520.2334.3205.6655606600.171
3000.06010.3940.6350.2542.9006.3376407500.153
4000.0470.3770.6140.2757.2006.7827208700.137
5000.03660.3660.5990.3071.5007.66481010000.125
6300.02830.3570.5820.3390.0908.64691011500.115

1. The code numbers to be read in conjuction with 06020711 at the beginning.

Code number for different types of insulation screen : replace the 6th digit as follows: 7 for STRIPPABLE + LEAD; 8 for BONDED + LEAD; 9 for GRAPHITE + LEAD

Example: for 150 mm² Strippable + Lead cable, the code number is 0602071116.

2. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

For other laying conditions, please refer to Table nos. 1 – 5 for derating factors.

  • UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=3.5/6(7.2) kV


  • UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=6/10(12) kV


  • UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=8.7/15(17.5) kV


  • UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=12/20(24) kV


  • UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=18/30(36) kV


  • UN-ARMOURED THREE CORE LEAD SHEATHED CABLE Uo/U (Um)=3.5/6(7.2) kV


  • UN-ARMOURED THREE CORE LEAD SHEATHED CABLE Uo/U (Um)=6/10(12) kV


  • UN-ARMOURED THREE CORE LEAD SHEATHED CABLE Uo/U (Um)=8.7/15(17.5) kV


  • UN-ARMOURED THREE CORE LEAD SHEATHED CABLE Uo/U (Um)=12/20(24) kV


  • UN-ARMOURED THREE CORE LEAD SHEATHED CABLE Uo/U (Um)=18/30(33) kV


  • ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=3.5/6(7.2) kV


  • ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=6/10(12) kV


  • ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=8.7/15(17.5) kV


  • ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=12/20(24) kV


  • ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=18/30(36) kV


  • ARMOURED THREE CORE LEAD SHEATHED CABLE Uo/U (Um)=3.5/6(7.2) kV


  • ARMOURED THREE CORE LEAD SHEATHED CABLE Uo/U (Um)=6/10(12) kV


  • ARMOURED THREE CORE LEAD SHEATHED CABLE Uo/U (Um)=8.7/15(17.5) kV


  • ARMOURED THREE CORE LEAD SHEATHED CABLE Uo/U (Um)=12/20(24) kV


  • ARMOURED THREE CORE LEAD SHEATHED CABLE Uo/U (Um)=18/30(36) kV

    ARMOURED THREE CORE LEAD SHEATHED CABLE

    COPPER CONDUCTORS

    STANDARD : IEC 60502-2

    Uo/U (Um)=18/30(36) kV

    • REQUEST A QUOTE
     

    Code Number (1)Nominal Cross SectionNominal Dia. of Cond.Weight of Cond.Nominal Insulation Thick.Approx. diameter over insulationNominal Lead Sheath Thick.Armour Steel Wire Dia.Nominal PVC Sheath Thick.Approx. External DiameterApprox. Weight of Cable
     mm²mmkg/kmmmmmmmmmmmmmkg/km
    12508.112608.025.32.53.153.69217300
    13709.718208.026.92.63.153.89819450
    149511.425188.028.62.73.153.910221500
    1512012.931758.030.12.83.154.010623400
    1615014.339198.031.52.93.154.111025300
    1718516.049028.033.23.03.154.211427750
    1824018.464438.035.63.13.154.412031150
    1930020.780698.038.13.23.154.612735050
    Nominal Cross SectionDC Resistance at 20°CNominal InductanceCapacitanceShort circuit current for 1 sec.Current Carrying Capacity(3)Voltage drop per phase
    ConductorScreen per phase (2)Under- ground CableCable in Air
    mm²ohm/kmmH/km µF/KmKAKAAAV/A/km
    500.3870.4490.147.1500.8692252300.497
    700.2680.4300.1610.0100.9332702800.372
    950.1930.4190.1713.5850.9883303450.292
    1200.1530.4050.1817.1601.0363703950.248
    1500.1240.3950.1921.4501.0814154500.217
    1850.09910.3840.2126.4551.1354655100.189
    2400.07540.3710.2334.3201.2125406000.163
    3000.06010.3580.2542.9001.2926106800.143

    1. The code numbers to be read in conjuction with 06020123 at the beginning and “L” at the end.

    Example: for 150 mm² the code number is 0602012316L

    Code number for different types of insulation screen : replace the 6th digit as follows: 2 for S + CUW; 3 for B + CUT; 4 for B + CUW; 5 for G + CUT and 6 for G + CUW

    2. For Copper Tape screen only.

    3. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

    For other laying conditions, please refer to Table nos. 1 – 5 for derating factors.